Battery bank for 1 kWh a day with 3 days of autonomy, 48 V flooded lead-acid
| Usable energy needed1 kWh a day × 3 days | 3kWh |
|---|---|
| Nominal capacity to buyusable ÷ (50% DoD × 80% round-trip) | 7.5kWh |
| Capacity at 48 V | 156Ah |
| 100 Ah blocks4 in series makes one 48 V string | 2blocks |
| Charge current0.12C — the charger and the array both have to deliver this | 19A |
| Depth of discharge usedmanufacturer figure for rated cycle life, not the physical limit | 50% |
| Round-trip efficiencyenergy lost on the way in and out again | 80% |
| Rated cycle lifeat 50% DoD | 600–1.200 cycles |
- Daily load
- 1 kWh
- Days of autonomy
- 3
- System voltage
- 48 V
- Chemistry
- flooded lead-acid
Two derates, not one
Pulling 1 kWh a day for 3 days means 3 kWh has to come out of the bank. That is not the number you buy.
Two things stand between nameplate capacity and delivered energy. Depth of discharge caps how much of the pack you are allowed to use if you want the rated cycle life — 50% here. Round-trip efficiency takes another 80% off, lost as heat on the way in and out.
Divide by both and the bank you actually buy is 7.5 kWh, or 156 Ah at 48 V.
Dividing by depth of discharge alone is the common mistake, and it is why so many banks fall short in their first winter.
What that looks like on a shelf
About 2 × 100 Ah blocks. The charger and the array both have to be able to push 19 A into it, which is the constraint people find after the batteries arrive rather than before.
Voltage is the cheap lever
156 Ah at 48 V is the same energy as a much larger amp-hour figure at 12 V, and current is what makes cable expensive. Every doubling of system voltage halves the current for the same power and quarters the loss in the wire.
Notes
- Two derates, not one. Dividing by depth of discharge alone is the usual mistake — the pack also loses 20% round-trip on Flooded lead-acid, and that comes off the top of every cycle.
- At 50% usable, Flooded lead-acid needs nearly twice the nameplate capacity of lithium for the same job. Compare on kWh delivered over the warranty, not on sticker price per kWh.
- 48 V is the practical floor for this size. Higher system voltage means proportionally lower current for the same power — 156 Ah at 48 V would be 625 Ah at 12 V, and the cable to carry it gets expensive fast.
- 3 days of autonomy covers 3× a normal day's use. Grid-tied backup normally carries one day; off-grid with no generator normally carries three to five, because that is what a run of overcast weather costs you.
Nearby sizes
- Battery bank for 2 kWh a day with 3 days of autonomy, 48 V flooded lead-acid
- Battery bank for 3 kWh a day with 3 days of autonomy, 48 V flooded lead-acid
- Battery bank for 1 kWh a day with 2 days of autonomy, 48 V flooded lead-acid
- Battery bank for 1 kWh a day with 4 days of autonomy, 48 V flooded lead-acid
- Battery bank for 1 kWh a day with 1 days of autonomy, 48 V flooded lead-acid
- Battery bank for 1 kWh a day with 5 days of autonomy, 48 V flooded lead-acid
- Battery bank for 1 kWh a day with 3 days of autonomy, 24 V flooded lead-acid
- Battery bank for 1 kWh a day with 3 days of autonomy, 12 V flooded lead-acid
- Battery bank for 1 kWh a day with 3 days of autonomy, 48 V AGM
- Battery bank for 1 kWh a day with 3 days of autonomy, 48 V LiFePO₄
Read more
- Roof Space for a 10 kW Array: Panel Area Is Not Roof AreaTwenty-five panels cover about 525 square feet. The roof they need is closer to 680, and the gap is mostly required by code rather than by geometry.
- Daily Solar Output by Region, and the Seasonal Swing Behind the AverageAn annual average tells you what the system produces over a year. It tells you almost nothing about December, and December is where the sizing arguments happen.
- How Many Panels for 1,000 kWh a MonthThe answer ranges from fifteen panels to thirty-four, for the same house using the same electricity. Location does most of that, panel wattage does the rest.
- Converting kW to Panels, and the Three Ratings That Get ConfusedThree different numbers on a solar quote are all measured in kilowatts and none of them mean the same thing. Knowing which is which makes quotes comparable.