ArrayBudgetPanels, batteries and inverters sized to the load you actually have.

System Sizing

Array, inverter and battery sized to the daily load you actually have, with real derate factors applied.

Array size is daily consumption divided by peak sun hours, divided again by a derate factor. The derate factor is where most estimates go wrong, and it is not a small correction.

0.77 is the PVWatts default from NREL. It bundles soiling, heat, wiring losses, module mismatch and inverter efficiency. Size an array without it and you will be short by roughly a quarter — which shows up as a system that meets its numbers in April and misses them all winter.

Peak sun hours is an annual average, and December is not average

Winter output across most of the US runs 40–60% of the annual average. A grid-tied system sized to the average is fine, because the grid covers the difference. An off-grid system sized the same way runs out in January.

Roof area is not panel area

The figures here give panel area. Add 15–25% for row spacing, fire setbacks and obstructions — and check the roof plane actually faces within about 45° of south. A due-east array is not a due-south array with a small penalty; it is a meaningfully different system.

The inverter is sized smaller than the array, on purpose

A DC-to-AC ratio around 1.2 is standard. Arrays hit their nameplate rating for only a few hours a year, so an inverter sized to peak DC output spends its life underloaded, which is both expensive and less efficient. Some clipping at midday in June is the correct trade.

What this does not size

Batteries, wire, and the loads themselves. Those are separate calculations, and each has a way of going wrong that array sizing does not reveal — a correctly sized array with undersized cable delivers a fraction of what it makes.

1 article

30 kWh a day, 4.5 peak sun hours, 400 W panels

Array size
8.8kW DC
22 × 400 W panels for 30 kWh a day
30 kWh/day · 4.5 sun hours22 panels · 8.8 kW · about 451 sq ft of roof11,130 kWh a year · 7.33 kW inverter
Panels (400 W each)22panels
Array size8.66 kW needed, rounded up to whole panels8.8kW DC
Roof area41.9 m² of panel, before spacing and setbacks451ft²
Inverter1.2:1 DC-to-AC ratio7.33kW AC
Battery (1 day backup)781 Ah at 48 V, 80% depth of discharge37.5kWh
Expected yearly output11,130kWh/yr
Derate factor appliedPVWatts default — soiling, heat, wiring, inverter0.77

Notes

  • 4.5 peak sun hours is a daily average across the year. Winter output in most of the US runs 40–60% of the annual average, so a system sized to the average will fall short in December unless you oversize or stay grid-tied.
  • Roof area here is panel area only. Add 15–25% for row spacing, fire setbacks and obstructions — and check that the roof plane actually faces within about 45° of south.
  • One day of battery backup covers an evening and a night. Off-grid systems with no generator normally carry three to five days.

Solar array sizing

84 calculations · browse all