ArrayBudgetPanels, batteries and inverters sized to the load you actually have.

Battery bank for 11 kWh a day with 4 days of autonomy, 48 V flooded lead-acid

Battery bank
110kWh nominal
2,292 Ah at 48 V — Flooded lead-acid, 4 days of autonomy
Usable energy needed11 kWh a day × 4 days44kWh
Nominal capacity to buyusable ÷ (50% DoD × 80% round-trip)110kWh
Capacity at 48 V2,292Ah
100 Ah blocks4 in series makes one 48 V string23blocks
Charge current0.12C — the charger and the array both have to deliver this275A
Depth of discharge usedmanufacturer figure for rated cycle life, not the physical limit50%
Round-trip efficiencyenergy lost on the way in and out again80%
Rated cycle lifeat 50% DoD600–1.200 cycles
Daily load
11 kWh
Days of autonomy
4
System voltage
48 V
Chemistry
flooded lead-acid

Two derates, not one

Pulling 11 kWh a day for 4 days means 44 kWh has to come out of the bank. That is not the number you buy.

Two things stand between nameplate capacity and delivered energy. Depth of discharge caps how much of the pack you are allowed to use if you want the rated cycle life — 50% here. Round-trip efficiency takes another 80% off, lost as heat on the way in and out.

Divide by both and the bank you actually buy is 110 kWh, or 2,292 Ah at 48 V.

Dividing by depth of discharge alone is the common mistake, and it is why so many banks fall short in their first winter.

What that looks like on a shelf

About 23 × 100 Ah blocks. The charger and the array both have to be able to push 275 A into it, which is the constraint people find after the batteries arrive rather than before.

Voltage is the cheap lever

2,292 Ah at 48 V is the same energy as a much larger amp-hour figure at 12 V, and current is what makes cable expensive. Every doubling of system voltage halves the current for the same power and quarters the loss in the wire.

Notes

  • Two derates, not one. Dividing by depth of discharge alone is the usual mistake — the pack also loses 20% round-trip on Flooded lead-acid, and that comes off the top of every cycle.
  • At 50% usable, Flooded lead-acid needs nearly twice the nameplate capacity of lithium for the same job. Compare on kWh delivered over the warranty, not on sticker price per kWh.
  • 48 V is the practical floor for this size. Higher system voltage means proportionally lower current for the same power — 2,292 Ah at 48 V would be 9,167 Ah at 12 V, and the cable to carry it gets expensive fast.
  • 4 days of autonomy covers 4× a normal day's use. Grid-tied backup normally carries one day; off-grid with no generator normally carries three to five, because that is what a run of overcast weather costs you.

Nearby sizes

Read more