Wire size for 10 A over 200 ft on a 48 V system

Smallest wire that works
4 AWGat 2.57% drop
10 A over 200 ft one-way on a 48 V system
Circuit power10 A × 48 V480W
Conductor length200 ft out and 200 ft back400ft
Ampacity alone would allow26.17% drop — legal on heat, not acceptable on drop14 AWG
Power lost in the cable2.57% of what you are sending12.3W
— Voltage drop by size —
14 AWG15 A rated, drop too high26.17%12.56 V
12 AWG20 A rated, drop too high16.5%7.92 V
10 AWG30 A rated, drop too high10.33%4.96 V
8 AWG50 A rated, drop too high6.48%3.11 V
6 AWG65 A rated, drop too high4.09%1.96 V
4 AWG85 A rated2.57%1.23 V
2 AWG115 A rated1.62%0.78 V
1/0 AWG150 A rated1.02%0.49 V
2/0 AWG175 A rated0.81%0.39 V
4/0 AWG230 A rated0.51%0.24 V
Current
10 A
One-way distance
200 ft
System voltage
48 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 10 A over 200 ft at 48 V, ampacity alone would allow 14 AWG. Voltage drop says 4 AWG — 2.57%, or 1.23 V of the 48 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 400 ft, not 200 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

480 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • Two different answers, and the bigger one wins. 14 AWG carries 10 A without overheating, but it drops 26.17% over this distance. You need 4 AWG — sized by voltage drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 48 V DC system it is already generous: 1.44 V of the 48 V you started with.
  • Running at 48 V is doing a lot of work here. The same 480 W at 12 V would draw 40 A and need a far heavier cable.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.