Wire size for 10 A over 60 ft on a 24 V system

Smallest wire that works
6 AWGat 2.46% drop
10 A over 60 ft one-way on a 24 V system
Circuit power10 A × 24 V240W
Conductor length60 ft out and 60 ft back120ft
Ampacity alone would allow15.7% drop — legal on heat, not acceptable on drop14 AWG
Power lost in the cable2.46% of what you are sending5.9W
— Voltage drop by size —
14 AWG15 A rated, drop too high15.7%3.77 V
12 AWG20 A rated, drop too high9.9%2.38 V
10 AWG30 A rated, drop too high6.2%1.49 V
8 AWG50 A rated, drop too high3.89%0.93 V
6 AWG65 A rated2.46%0.59 V
4 AWG85 A rated1.54%0.37 V
2 AWG115 A rated0.97%0.23 V
1/0 AWG150 A rated0.61%0.15 V
2/0 AWG175 A rated0.48%0.12 V
4/0 AWG230 A rated0.3%0.07 V
Current
10 A
One-way distance
60 ft
System voltage
24 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 10 A over 60 ft at 24 V, ampacity alone would allow 14 AWG. Voltage drop says 6 AWG — 2.46%, or 0.59 V of the 24 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 120 ft, not 60 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

240 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • Two different answers, and the bigger one wins. 14 AWG carries 10 A without overheating, but it drops 15.7% over this distance. You need 6 AWG — sized by voltage drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 24 V DC system it is already generous: 0.72 V of the 24 V you started with.
  • Running at 24 V is doing a lot of work here. The same 240 W at 12 V would draw 20 A and need a far heavier cable.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.