ArrayBudgetPanels, batteries and inverters sized to the load you actually have.

Wire size for 100 A over 200 ft on a 48 V system

Smallest wire that works
over 4/0
100 A over 200 ft at 48 V exceeds 3% even on 4/0 — split the run or raise the voltage
Circuit power100 A × 48 V4,800W
Conductor length200 ft out and 200 ft back400ft
Ampacity alone would allow16.17% drop — legal on heat, not acceptable on drop2 AWG
— Voltage drop by size —
14 AWGnot rated for 100 A — 15 A max
12 AWGnot rated for 100 A — 20 A max
10 AWGnot rated for 100 A — 30 A max
8 AWGnot rated for 100 A — 50 A max
6 AWGnot rated for 100 A — 65 A max
4 AWGnot rated for 100 A — 85 A max
2 AWG115 A rated, drop too high16.17%7.76 V
1/0 AWG150 A rated, drop too high10.17%4.88 V
2/0 AWG175 A rated, drop too high8.06%3.87 V
4/0 AWG230 A rated, drop too high5.07%2.43 V
Current
100 A
One-way distance
200 ft
System voltage
48 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 100 A over 200 ft at 48 V, ampacity alone would allow 2 AWG. Voltage drop says larger than 4/0 — %, or V of the 48 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 400 ft, not 200 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

4,800 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • At this length ampacity and voltage drop point at the same wire, which is unusual. Runs over about 20 ft at low DC voltage are normally decided by drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 48 V DC system it is already generous: 1.44 V of the 48 V you started with.
  • Running at 48 V is doing a lot of work here. The same 4,800 W at 12 V would draw 400 A and need a far heavier cable.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.

Nearby sizes

Read more