ArrayBudgetPanels, batteries and inverters sized to the load you actually have.

Wire size for 125 A over 300 ft on a 48 V system

Smallest wire that works
over 4/0
125 A over 300 ft at 48 V exceeds 3% even on 4/0 — split the run or raise the voltage
Circuit power125 A × 48 V6,000W
Conductor length300 ft out and 300 ft back600ft
Ampacity alone would allow19.06% drop — legal on heat, not acceptable on drop1/0 AWG
— Voltage drop by size —
14 AWGnot rated for 125 A — 15 A max
12 AWGnot rated for 125 A — 20 A max
10 AWGnot rated for 125 A — 30 A max
8 AWGnot rated for 125 A — 50 A max
6 AWGnot rated for 125 A — 65 A max
4 AWGnot rated for 125 A — 85 A max
2 AWGnot rated for 125 A — 115 A max
1/0 AWG150 A rated, drop too high19.06%9.15 V
2/0 AWG175 A rated, drop too high15.11%7.25 V
4/0 AWG230 A rated, drop too high9.5%4.56 V
Current
125 A
One-way distance
300 ft
System voltage
48 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 125 A over 300 ft at 48 V, ampacity alone would allow 1/0 AWG. Voltage drop says larger than 4/0 — %, or V of the 48 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 600 ft, not 300 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

6,000 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • At this length ampacity and voltage drop point at the same wire, which is unusual. Runs over about 20 ft at low DC voltage are normally decided by drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 48 V DC system it is already generous: 1.44 V of the 48 V you started with.
  • Running at 48 V is doing a lot of work here. The same 6,000 W at 12 V would draw 500 A and need a far heavier cable.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.

Nearby sizes

Read more