Wire size for 15 A over 250 ft on a 48 V system

Smallest wire that works
1/0 AWGat 1.91% drop
15 A over 250 ft one-way on a 48 V system
Circuit power15 A × 48 V720W
Conductor length250 ft out and 250 ft back500ft
Ampacity alone would allow49.06% drop — legal on heat, not acceptable on drop14 AWG
Power lost in the cable1.91% of what you are sending13.7W
— Voltage drop by size —
14 AWG15 A rated, drop too high49.06%23.55 V
12 AWG20 A rated, drop too high30.94%14.85 V
10 AWG30 A rated, drop too high19.38%9.3 V
8 AWG50 A rated, drop too high12.16%5.83 V
6 AWG65 A rated, drop too high7.67%3.68 V
4 AWG85 A rated, drop too high4.81%2.31 V
2 AWG115 A rated, drop too high3.03%1.46 V
1/0 AWG150 A rated1.91%0.92 V
2/0 AWG175 A rated1.51%0.73 V
4/0 AWG230 A rated0.95%0.46 V
Current
15 A
One-way distance
250 ft
System voltage
48 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 15 A over 250 ft at 48 V, ampacity alone would allow 14 AWG. Voltage drop says 1/0 AWG — 1.91%, or 0.92 V of the 48 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 500 ft, not 250 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

720 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • Two different answers, and the bigger one wins. 14 AWG carries 15 A without overheating, but it drops 49.06% over this distance. You need 1/0 AWG — sized by voltage drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 48 V DC system it is already generous: 1.44 V of the 48 V you started with.
  • Running at 48 V is doing a lot of work here. The same 720 W at 12 V would draw 60 A and need a far heavier cable.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.