Wire size for 175 A over 75 ft on a 24 V system

Smallest wire that works
over 4/0
175 A over 75 ft at 24 V exceeds 3% even on 4/0 — split the run or raise the voltage
Circuit power175 A × 24 V4,200W
Conductor length75 ft out and 75 ft back150ft
Ampacity alone would allow10.58% drop — legal on heat, not acceptable on drop2/0 AWG
— Voltage drop by size —
14 AWGnot rated for 175 A — 15 A max
12 AWGnot rated for 175 A — 20 A max
10 AWGnot rated for 175 A — 30 A max
8 AWGnot rated for 175 A — 50 A max
6 AWGnot rated for 175 A — 65 A max
4 AWGnot rated for 175 A — 85 A max
2 AWGnot rated for 175 A — 115 A max
1/0 AWGnot rated for 175 A — 150 A max
2/0 AWG175 A rated, drop too high10.58%2.54 V
4/0 AWG230 A rated, drop too high6.65%1.6 V
Current
175 A
One-way distance
75 ft
System voltage
24 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 175 A over 75 ft at 24 V, ampacity alone would allow 2/0 AWG. Voltage drop says larger than 4/0 — %, or V of the 24 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 150 ft, not 75 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

4,200 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • At this length ampacity and voltage drop point at the same wire, which is unusual. Runs over about 20 ft at low DC voltage are normally decided by drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 24 V DC system it is already generous: 0.72 V of the 24 V you started with.
  • Running at 24 V is doing a lot of work here. The same 4,200 W at 12 V would draw 350 A and need a far heavier cable.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.