Wire size for 20 A over 20 ft on a 48 V system

Smallest wire that works
10 AWGat 2.07% drop
20 A over 20 ft one-way on a 48 V system
Circuit power20 A × 48 V960W
Conductor length20 ft out and 20 ft back40ft
Ampacity alone would allow3.3% drop — legal on heat, not acceptable on drop12 AWG
Power lost in the cable2.07% of what you are sending19.8W
— Voltage drop by size —
14 AWGnot rated for 20 A — 15 A max
12 AWG20 A rated, drop too high3.3%1.58 V
10 AWG30 A rated2.07%0.99 V
8 AWG50 A rated1.3%0.62 V
6 AWG65 A rated0.82%0.39 V
4 AWG85 A rated0.51%0.25 V
2 AWG115 A rated0.32%0.16 V
1/0 AWG150 A rated0.2%0.1 V
2/0 AWG175 A rated0.16%0.08 V
4/0 AWG230 A rated0.1%0.05 V
Current
20 A
One-way distance
20 ft
System voltage
48 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 20 A over 20 ft at 48 V, ampacity alone would allow 12 AWG. Voltage drop says 10 AWG — 2.07%, or 0.99 V of the 48 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 40 ft, not 20 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

960 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • Two different answers, and the bigger one wins. 12 AWG carries 20 A without overheating, but it drops 3.3% over this distance. You need 10 AWG — sized by voltage drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 48 V DC system it is already generous: 1.44 V of the 48 V you started with.
  • Running at 48 V is doing a lot of work here. The same 960 W at 12 V would draw 80 A and need a far heavier cable.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.