Wire size for 100 A over 5 ft on a 12 V system

Smallest wire that works
2 AWGat 1.62% drop
100 A over 5 ft one-way on a 12 V system
Circuit power100 A × 12 V1,200W
Conductor length5 ft out and 5 ft back10ft
Ampacity alone would allow1.62% drop — legal on heat, and fine on drop2 AWG
Power lost in the cable1.62% of what you are sending19.4W
— Voltage drop by size —
14 AWGnot rated for 100 A — 15 A max
12 AWGnot rated for 100 A — 20 A max
10 AWGnot rated for 100 A — 30 A max
8 AWGnot rated for 100 A — 50 A max
6 AWGnot rated for 100 A — 65 A max
4 AWGnot rated for 100 A — 85 A max
2 AWG115 A rated1.62%0.19 V
1/0 AWG150 A rated1.02%0.12 V
2/0 AWG175 A rated0.81%0.1 V
4/0 AWG230 A rated0.51%0.06 V
Current
100 A
One-way distance
5 ft
System voltage
12 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 100 A over 5 ft at 12 V, ampacity alone would allow 2 AWG. Voltage drop says 2 AWG — 1.62%, or 0.19 V of the 12 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 10 ft, not 5 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

1,200 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • At this length ampacity and voltage drop point at the same wire, which is unusual. Runs over about 20 ft at low DC voltage are normally decided by drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 12 V DC system it is already generous: 0.36 V of the 12 V you started with.
  • 12 V is what makes this expensive. The same 1,200 W at 24 V halves the current and quarters the loss — the cheapest way out of a big cable bill is almost always a higher system voltage.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.