Wire size for 20 A over 200 ft on a 12 V system

Smallest wire that works
over 4/0
20 A over 200 ft at 12 V exceeds 3% even on 4/0 — split the run or raise the voltage
Circuit power20 A × 12 V240W
Conductor length200 ft out and 200 ft back400ft
Ampacity alone would allow132% drop — legal on heat, not acceptable on drop12 AWG
— Voltage drop by size —
14 AWGnot rated for 20 A — 15 A max
12 AWG20 A rated, drop too high132%15.84 V
10 AWG30 A rated, drop too high82.67%9.92 V
8 AWG50 A rated, drop too high51.87%6.22 V
6 AWG65 A rated, drop too high32.73%3.93 V
4 AWG85 A rated, drop too high20.53%2.46 V
2 AWG115 A rated, drop too high12.93%1.55 V
1/0 AWG150 A rated, drop too high8.13%0.98 V
2/0 AWG175 A rated, drop too high6.45%0.77 V
4/0 AWG230 A rated, drop too high4.05%0.49 V
Current
20 A
One-way distance
200 ft
System voltage
12 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 20 A over 200 ft at 12 V, ampacity alone would allow 12 AWG. Voltage drop says larger than 4/0 — %, or V of the 12 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 400 ft, not 200 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

240 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • At this length ampacity and voltage drop point at the same wire, which is unusual. Runs over about 20 ft at low DC voltage are normally decided by drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 12 V DC system it is already generous: 0.36 V of the 12 V you started with.
  • 12 V is what makes this expensive. The same 240 W at 24 V halves the current and quarters the loss — the cheapest way out of a big cable bill is almost always a higher system voltage.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.