Wire size for 30 A over 30 ft on a 12 V system

Smallest wire that works
2 AWGat 2.91% drop
30 A over 30 ft one-way on a 12 V system
Circuit power30 A × 12 V360W
Conductor length30 ft out and 30 ft back60ft
Ampacity alone would allow18.6% drop — legal on heat, not acceptable on drop10 AWG
Power lost in the cable2.91% of what you are sending10.5W
— Voltage drop by size —
14 AWGnot rated for 30 A — 15 A max
12 AWGnot rated for 30 A — 20 A max
10 AWG30 A rated, drop too high18.6%2.23 V
8 AWG50 A rated, drop too high11.67%1.4 V
6 AWG65 A rated, drop too high7.36%0.88 V
4 AWG85 A rated, drop too high4.62%0.55 V
2 AWG115 A rated2.91%0.35 V
1/0 AWG150 A rated1.83%0.22 V
2/0 AWG175 A rated1.45%0.17 V
4/0 AWG230 A rated0.91%0.11 V
Current
30 A
One-way distance
30 ft
System voltage
12 V

Ampacity and voltage drop are two different questions

Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.

For 30 A over 30 ft at 12 V, ampacity alone would allow 10 AWG. Voltage drop says 2 AWG — 2.91%, or 0.35 V of the 12 V you started with.

Why the distance doubles

Current goes out on one conductor and comes back on the other. The copper in the circuit is 60 ft, not 30 ft. Forgetting the return leg is how people arrive at exactly half the real drop.

Why it matters more than it sounds

360 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulphates its way to an early death while every meter in the system reads normal.

What is not in the table

Copper at 75 °C. Aluminium conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.

Notes

  • Two different answers, and the bigger one wins. 10 AWG carries 30 A without overheating, but it drops 18.6% over this distance. You need 2 AWG — sized by voltage drop, not by heat.
  • 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 12 V DC system it is already generous: 0.36 V of the 12 V you started with.
  • 12 V is what makes this expensive. The same 360 W at 24 V halves the current and quarters the loss — the cheapest way out of a big cable bill is almost always a higher system voltage.
  • Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.