Wire size for 30 A over 40 ft on a 12 V system
| Circuit power30 A × 12 V | 360W |
|---|---|
| Conductor length40 ft out and 40 ft back | 80ft |
| Ampacity alone would allow24.8% drop — legal on heat, not acceptable on drop | 10 AWG |
| Power lost in the cable2.44% of what you are sending | 8.8W |
| — Voltage drop by size — | |
| 14 AWGnot rated for 30 A — 15 A max | — |
| 12 AWGnot rated for 30 A — 20 A max | — |
| 10 AWG30 A rated, drop too high | 24.8%2.98 V |
| 8 AWG50 A rated, drop too high | 15.56%1.87 V |
| 6 AWG65 A rated, drop too high | 9.82%1.18 V |
| 4 AWG85 A rated, drop too high | 6.16%0.74 V |
| 2 AWG115 A rated, drop too high | 3.88%0.47 V |
| 1/0 AWG150 A rated | 2.44%0.29 V |
| 2/0 AWG175 A rated | 1.93%0.23 V |
| 4/0 AWG230 A rated | 1.22%0.15 V |
Notes
- Two different answers, and the bigger one wins. 10 AWG carries 30 A without overheating, but it drops 24.8% over this distance. You need 1/0 AWG — sized by voltage drop, not by heat.
- 3% is the NEC informational recommendation for a branch circuit, not a hard rule. On a 12 V DC system it is already generous: 0.36 V of the 12 V you started with.
- 12 V is what makes this expensive. The same 360 W at 24 V halves the current and quarters the loss — the cheapest way out of a big cable bill is almost always a higher system voltage.
- Figures are copper at 75 °C. Aluminium runs about 60% of copper conductivity — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundling all derate ampacity further, and none of that is in this table.
Ampacity and voltage drop are two different questions
Ampacity asks whether the wire gets hot enough to be dangerous. Voltage drop asks whether enough of the power arrives at the other end. On a low-voltage DC run they almost never give the same answer, and the bigger one wins.
For 30 A over 40 ft at 12 V, ampacity alone would allow 10 AWG. Voltage drop says 1/0 AWG — 2.44%, or 0.29 V of the 12 V you started with.
Why the distance doubles
Current goes out on one conductor and comes back on the other. The copper in the circuit is 80 ft, not 40 ft. Forgetting the return leg is how people arrive at exactly half the real drop.
Why it matters more than it sounds
360 W leaves the source. Undersized cable does not just waste a few percent — on a solar charge controller it means the battery never sees absorption voltage, never finishes a charge cycle, and sulfates its way to an early death while every meter in the system reads normal.
What is not in the table
Copper at 75 °C. Aluminum conducts about 60% as well — go up two sizes. Conduit fill, ambient temperature above 30 °C and bundled conductors all derate ampacity further.
Nearby sizes
- Wire size for 25 A over 40 ft on a 12 V system
- Wire size for 40 A over 40 ft on a 12 V system
- Wire size for 20 A over 40 ft on a 12 V system
- Wire size for 50 A over 40 ft on a 12 V system
- Wire size for 30 A over 30 ft on a 12 V system
- Wire size for 30 A over 50 ft on a 12 V system
- Wire size for 30 A over 25 ft on a 12 V system
- Wire size for 30 A over 60 ft on a 12 V system
Read more
- Backup Generator vs Solar Battery — Cost per Hour of Outage CoveredA battery is cheaper to own and runs out. A generator is cheaper to run and never does. Which one wins is decided by how long your outages actually last.
- Solar Cost per Watt — the Only Unit That Makes Two Quotes ComparableTwo quotes for "a solar system" are not comparable. Two quotes at dollars per watt are, and the conversion takes one division.
- Solar Payback Period — the Four Inputs, and the One That Decides ItPayback is one division with four inputs. Three of them are knowable to within a few percent. The fourth — what your utility pays for exports — swings the answer by more than a decade.
- Home Solar Battery Cost — Priced per Usable Kilowatt-HourStorage is the worst-value component of a solar system on pure energy arithmetic, and often the right purchase anyway. Which of those is true depends on why you are buying it.